Note the stick inserted in the drop tube. A trained Class A/B operator would know this disables the flapper and is a serious filling hazard.
Note the large crack in the bottom of the spill bucket: A trained Class A/B operator would know this is bad.
Follow the yellow fiberglass pipe as it exits the sump and you'll notice...no penetration fitting. Any liquid accumulation drains right out the sump.
The stage 1 poppets are supposed to be attached to the tank top, not the vents, per recommended practices. This is a poor man's retrofit and we checked with a few experts and though horizontally placed rather than the usual vertical, it should work...so long as the return hose reaches this area.