The lid indicates a groundwater monitor well opening but it is unclear what this "mystery" riser does. Or why it's full of debris.
The after-installation zip tie above the water float will restrict the float from rising very high up, giving inaccurate high water readings.
The sump sensor not in the correct position. It should be vertical so the float will work.
Outer skin of flexible plastic piping is not aging well.
Read the sign closely... If pump runs slow...has the mechanical line leak detector found a 3 gph leak?