Not sure. Something about both turbines and one downstream MLLD seems a bit off but cannot figure the exact issue.
Also, the sensor appears to be up higher than it should but it might be very long, just cannot see it.
Hi Dean. You’re very close. The LLD is upstream of the turbine pump, so the line is not protected for a 3 gallon per hour leak between the LLD and the turbine. Can’t see the bottom of the sensor so don’t know if it’s on the bottom or not.