Notice the copper tubing curling from 6 o'clock counter clockwise up to about 11 o'clock? It doesn't go anywhere. That's because someone removed the mechanical leak detector, which was probably in slow flow and irritating the customers. In our training we warn folks not to do this. In fact we learned last year about a $15,000 fine from a state UST agency to a UST operator who did just that.

can’t say about the sump but the picture is over exposed toward the sunny side and under exposed toward whatever is going on in the sump
Hi William. If you look at the bottom of the turbine pump, around 7 o’clock, the one plug with the silver square in the circle is where the automatic line leak detector should be. Someone removed it and plugged it so there’s no way to look for a 3 GPH leak in the pressurized piping.