Hi, this is Ben Thomas with UST training this is a tank savvy minute. Your lines versus your tanks are more likely to leak if you have a leaky underground storage tank system in other words nine times out of 10 is probably the piping that’s going to leak and not the tank. How do we look for leaks in our modern UST system. I’ll give you a little pro tip here click on the little downward arrow we’re going to click on the lines feature. This shows us there are four pressurized lines and I’m going to click on the first one regular line and what I’m seeing here is that the pump is on, the pump is running and importantly it’s actually got three tests that the electronic line leak detector is doing. It’s doing a gross 3 gallon per hour leak test pass this morning, it can do a monthly 0.2 gallon per hour leak test pass that was yesterday, and it can do an annual 0.1 gallon per hour leak test and that was done about a week and a half ago. So, we know we have electronic line leak detectors, we know it’s programming to look for the large, medium, and small leaks and we know everything is functioning properly. This is Ben Thomas with UST training this has been a tank Savvy minute about electronic line leak detectors.